OCV Valve Functions

Series 94 Diaphragm Check Valve

Series 94 Diaphragm Check Valve The Series 94 is designed to open wide as long as inlet pressure exceeds discharge pressure. Should pressure reversal occur, control tubing in the valve carries back pressure to the bonnet forcing the valve closed. Also available as the 94-1 Check With Opening Speed Control; the 94-2 With Closing Speed Control and the 94-3 With Opening and Closing Speed Control.

Series 108 Pressure Relief Valve

Series 108 Pressure Relief Valve 108-2 is specifically designed for piping systems where constant line pressure is critical. When used in a main flow line it acts as a pressure sustaining valve. Used in a by-pass line it functions as a pressure relief valve. Combinations: 108-3 Pressure Relief/Back Pressure/Check and 108-4 Pressure Relief/Back Pressure/Solenoid. Also available as the Model 108FC for Fire Pump Relief; UL listed.

Series 108 Pressure Relief Valve

Series 108 Pressure Relief Valve The 110 is designed to maintain a constant pressure differential between any two points in a system where closing the valve directly causes the differential pressure to increase. The operation of the valve is modulated through a normally closed pilot control system that senses pressure between the two points across which the differential is to be maintained. Operation is automatic and settings are easily changed by adjusting the pilot control.

Series 115 Solenoid Control Valve

Series 115 Solenoid Control Valve The 115-2 Solenoid Control Valve was specifically designed to provide remote control of fluids. The valve operates fully open or tightly closed and, via the solenoid, can be triggered by such devices as clocks, timers, relays, probes, pressure or temperature sensors. Also available as the 115-4 Solenoid Control/3-Way Pilot/Auxiliary Assembly consisting of a high capacity valve with a packless 3-way solenoid pilot.

Series 118 Surge Anticipation Valve

Series 118 Surge Anticipation Valve The Series 118 is specifically designed to correct a common flow problem in pipeline systems -- low and high pressure waves. Installed in a by-pass line, the 118 opens on a low pressure signal within the flow and remains open for an (adjustable) interval that relieves the following high pressure surge.

Series 120 Rate of Flow Valve

Series 120 Rate of Flow Valve The Model 120-G is designed to maintain a constant preset rate of flow regardless of pressure fluctuations on either the upstream or downstream sides. the valve is controlled by a double acting diaphragm pilot with an adjustable spring for presetting the desired flow rate. Also available as the 120-G1 Rate of Flow/Solenoid Shut-Off and the 120-G2 Rate of flow/Pressure Reducing.

Series 125/126 Pump Control Valve

Series 125/126 Pump Control Valve OCV offers two pump control valves -- the 125 for booster pumps, and the 126 for deep well pumps. The basic function of both is to eliminate line surge when the pump starts and stops, and to prevent ump cavitation. To accomplish this, the valve is electrically interlocked with the pump motor and equipped for controlled opening and closing in coordination with the pump. The 125 installs on the main discharge line of the pump. The 126 installs in a by-pass line. Valve and pump are isolated from the distribution system by a slow-opening check valve.

Series 127 Pressure Reducing Valve

Series 127 Pressure Reducing Valve The Model 127-3 automatically reduces higher upstream pressure to a constant lower downstream pressure regardless of changes in supply or demand. If downstream pressure exceeds pilot preset, the valve modulates until downstream pressure is acceptable. Also available as the 127-2 Reducing/Sustaining; 127-4 Reducing/Check; 127-80 Reducing/Solenoid Shut-Off; 127-420 Reducing/Sustaining/Check and the 127-5 Reducing/Surge Control.

Series 3330 Altitude Valve

Series 3330 Altitude Valve The OCV Altitude Control Valve is offered in one-way (3331) and two-way (3333) models. Designed to control water levels in elevated towers, tanks and reservoirs from 10 to 200 feet, the valves operate on the differential in pressure between the height of the water and an adjustable spring loaded pilot on the valve. The valves install at ground level and when properly adjusted consistently maintain water levels with 4" of set point.

Series 22/88 Electronic Digital Control Valve

Series 22/88 Electronic Digital Control Valve The OCV Series 88 Digital Electronic Control Valve represents a totally new and unique approach to the problems of pressure, level, temperature or flow control. The combine the accuracy and sophistication of modern digital electronics with the simplicity of design and operation of diaphragm-actuated, line pressure-operated control valves. It is available in two basic versions: the Model 88 for use with a customer-supplied set point controller, and the Model 88C, with its own unique built-in controller. Either way, the net result is a design that is easy to startup, adjust and maintain, while at the same time offering unparalleled reliability, accuracy and stability.

Series 8000 Float Controlled Valve

Series 8000 Float Controlled Valve Designed to control liquid levels in tanks, ponds and similar reservoirs, the Series 8000 is equipped so that the float pilot closes the valve at the upper stop, opens it at the lower stop. A remote pilot may be used where it is impractical to install the valve close to the reservoir. Also, the pilot may be ordered to position the float in-line or perpendicular to the valve. Automatic operation is fully hydraulic with no mechanical or electrical linkage between the pilot and the valve.

66TS Tank Safety Valve

66TS Tank Safety Valve The OCV 66TS is designed to safely, effectively and automatically isolate a storage tank from its loading terminal or product transfer point. Hydraulically linked to the delivery pump, the valve automatically opens when the pump starts, closes when it stops, or line ruptures, providing anti-siphon protection. In this way, tank, pump, product and personnel are protected against accidents that can occur when manual tank shut-off valves are used. It can be used in any fluid handling system compatible with the pressure and materials parameters of diaphragm type valves.

Home | Feedback| Contents | Search | News | Products

Filters | Suppliers |Our Products | Gloves | Oil-Water Separator | Service Model | Slim Line

Tools | Cla-Val Valves | Pipe Handling | Cathodic Protection | Pipeline Equipment | PLIDCO Pipeline Repair | Poly-Pigs | OCV Valve Function | Filtration

Send mail to webmaster@drshannonco.com with questions or comments about this web site.
Copyright © 2006   D. R. Shannon Company
Last modified: March 21, 2008